Skip to calculator

🔌 Wire Size Calculator

Find the minimum wire gauge (AWG) for any circuit — from load current, run length, voltage, and conductor material. Checks both NEC ampacity and the 3% voltage-drop limit, for copper and aluminum. Free, no sign-up.

✓ Minimum AWG by NEC ampacity ✓ Voltage-drop check built in ✓ Free — no sign-up needed
📌 Quick Answer

A wire size calculator finds the smallest wire gauge that can safely carry a given load. It checks two things: the conductor's ampacity — how much current it can carry per NEC Table 310.16 — and the voltage drop over the run. The correct wire size is whichever of the two is larger. The core checks are:

Ampacity: NEC rating ≥ load current  |  Voltage drop: 2 × I × R × length ≤ 3% × V  |  Wire size = larger of the two

How to size a wire in 3 steps:

  1. Enter the load current, voltage, one-way distance, and conductor material.
  2. Pick the termination rating (75°C is typical) and your max voltage drop (3% by default).
  3. Click Calculate for the recommended AWG, with ampacity headroom and the resulting drop %.

For example, a 50 A load at 240 V over a 100-foot copper run needs 8 AWG — it carries 50 A at the 75°C rating and drops just 2.6%, within the 3% limit.

Wire Size Calculator

Enter load current, distance and material — get the minimum AWG wire size.

📊 NEC ampacity + voltage drop — copper & aluminum
V
A
ft
%
Distance is the one-way run to the load — the calculator accounts for the return conductor. The recommended size is the larger of the ampacity and voltage-drop results.
Recommended Wire Size
gauge
drop
Voltage
Current
Distance
Ampacity (this size)
By Ampacity
By Voltage Drop
Drop Check
Voltage Drop at This Size
%
V lost ·
Where the Voltage Goes at the Recommended Size
Supply
Drop
At Load
Enter your circuit and calculate to see the recommended wire size.
Ampacity values follow NEC Table 310.16; voltage drop is exact arithmetic from standard conductor resistance. This is an estimating aid — real installations must account for derating, conduit fill and terminations. Always follow local electrical code and a licensed electrician for final wire sizing.
⚡ Wire Sizing Made Simple

Know the Right Wire Size –
Before You Pull the Cable

Pick a wire too small and it overheats; too small for the distance and the voltage sags. This free calculator turns your load, run length, voltage and material into the minimum AWG — checking both NEC ampacity and the 3% voltage-drop limit, and recommending the larger of the two.

⚡ Try the Calculator Now
2
checks: ampacity + drop
75°C
typical termination rating
3%
voltage-drop limit
16
sizes, 14 AWG–500 kcmil
📖 Introduction

The Right Wire Size Is Two Questions, Not One

Choosing a wire gauge feels like it should be one lookup, but it is really two. The wire has to carry the current without overheating, and it has to deliver that current over the distance without the voltage sagging too far. The correct size is whichever of those two answers is larger.

The first question is ampacity — the current a conductor can carry continuously without overheating, fixed by the NEC for each size, material and temperature rating. The second is voltage drop — the voltage lost to the wire's resistance over the run, which grows with distance and current. A gauge can be perfectly safe for the amps and still drop too much voltage over a long pull.

This Wire Size Calculator answers both at once. Enter the load current, voltage, one-way distance and material; it finds the smallest AWG that meets the NEC ampacity table and the smallest that stays under your voltage-drop limit, then recommends whichever is larger — the size that satisfies both rules.

Pro Tip: On short runs, ampacity almost always sets the size. On runs past about 50 feet — especially at 120 V — voltage drop quietly takes over and pushes you a size or two larger than the amps alone would suggest. That crossover is exactly what this calculator pins down for you.
⚙️ How It Works

How the Wire Size Calculator Works

Fill in the circuit, click once. Here is what each field does and how the recommendation is reached.

1

Set Phase & Material

Choose DC, AC single-phase, or AC three-phase, and whether the conductor is copper or aluminum. Each combination changes both the ampacity and the voltage-drop math.

🟠 Copper carries more current than aluminum of the same size.
2

Pick the Termination Rating

60, 75, or 90°C — the rating of the terminals the wire lands on. Most modern breakers and lugs are 75°C, which is the default and the safe choice when unsure.

🌡️ Sizing follows the lowest-rated part in the circuit.
3

Enter Voltage & Load Current

The system voltage (12, 120, 240, 480…) and the current the load draws in amps. Ampacity is checked against the amps; the drop is measured against the voltage.

⚡ More amps push the size up on both counts.
4

Enter the One-Way Distance

The distance from the source to the load, measured one direction only. The calculator doubles it for the return conductor on DC and single-phase circuits.

5

Set the Max Voltage Drop

The drop limit you want to hold to — 3% by default, the NEC branch-circuit recommendation. Tighten it to 2% for sensitive electronics or long low-voltage runs.

✅ 3% branch · 5% feeder + branch combined
6

Calculate — Read the Size

You get the recommended AWG, the size required by ampacity, the size required by voltage drop, the ampacity headroom, and the resulting drop at the chosen gauge.

📐 Recommended = larger of the two required sizes
Reality Check: This tool sizes for ampacity and voltage drop — the two checks that set the gauge in the great majority of runs. It does not apply conductor-bundling or ambient-temperature derating, conduit fill, or the dwelling-service allowances of NEC 310.12. On a loaded or bundled install, confirm the result against the full code.
🔬 The Method

How Wire Sizing Works: Ampacity and Voltage Drop

Two independent checks decide the gauge. The calculator runs both and takes the larger result.

Check 1 — ampacity. Every wire size has an ampacity: the current it can carry continuously without its insulation overheating. The NEC fixes these values in Table 310.16 for each material and temperature rating. The calculator scans from the smallest gauge up and picks the first one whose ampacity meets your load current. That is the safety floor.

Check 2 — voltage drop. Drop is Ohm's law over the run: 2 × current × resistance-per-foot × one-way distance for DC and single-phase (the 2 covers the return conductor), or √3 × the rest for three-phase. The calculator finds the smallest gauge whose drop stays under your limit, expressed as a percentage of the supply voltage.

Taking the larger. The two checks rarely agree. Short runs are limited by ampacity; long runs by voltage drop. The recommended size is whichever is bigger, because the wire must clear both hurdles. The result panel labels which one was binding so you can see why.

A worked example. A 50-amp load at 240 V, copper, 100 feet one-way. Ampacity needs 8 AWG (rated 50 A at 75°C). Voltage drop on 8 AWG is 2 × 50 × 0.628 × (100 ÷ 1000) = 6.28 V, or 2.6% of 240 V — under the 3% limit. Both checks land on 8 AWG, so 8 AWG is the answer.

Parallel conductor sets change the drop term. Running two identical sets side by side halves the effective resistance, which halves the drop — useful on large feeders. Enable Advanced mode to set the number of sets; the calculator divides the resistance accordingly before checking the limit.

Why higher voltage needs smaller wire: The same volts lost is a tiny fraction of 480 V but a large fraction of 12 V. That is why a 240 V circuit can use a smaller conductor than a 120 V one for the same load and distance — and why 12 V DC runs need surprisingly heavy wire over even short distances.
📊 Wire Size Charts

Wire Size by Amps & Ampacity Charts

The quick lookup most people want first — wire size by amperage — plus the ampacity and resistance values the calculator works from.

Wire Size by Amperage (Copper & Aluminum, 75°C)

Load CurrentCopper AWGAluminum AWGCommon Use
15 A14 AWG12 AWGLighting, general receptacles
20 A12 AWG10 AWGKitchen & bathroom circuits
30 A10 AWG8 AWGDryer, water heater, A/C
40 A8 AWG8 AWGRange, large A/C
50 A8 AWG6 AWGRange, EV charger, subpanel
60 A6 AWG4 AWGSmall subpanel, hot tub
100 A3 AWG1 AWGSubpanel feeder
150 A1/0 AWG3/0 AWGLarge feeder
200 A3/0 AWG250 kcmilMain service feeder

These are NEC Table 310.16 sizes at the 75°C column, with the small-conductor limits of NEC 240.4(D) applied (14 AWG max 15 A, 12 AWG max 20 A, 10 AWG max 30 A copper) — the size needed to carry the current on a short run. Long runs may need a larger gauge for voltage drop, which is what the calculator above checks. Note that dwelling service and feeder conductors may use the reduced sizes allowed by NEC 310.12 (for example, 4 AWG copper or 2 AWG aluminum for a 100-amp dwelling service).

Conductor Resistance (Ω per 1000 ft)

Wire SizeCopper (Ω/1000 ft)Aluminum (Ω/1000 ft)
14 AWG3.075.06
12 AWG1.933.18
10 AWG1.212.00
8 AWG0.7641.26
6 AWG0.4910.808
4 AWG0.3080.508
2 AWG0.1940.319
1/0 AWG0.1220.201
2/0 AWG0.09670.159
4/0 AWG0.06080.100

Reading the resistance table: a smaller AWG number is a thicker wire with lower resistance, so it drops less voltage. Aluminum runs about 1.6× the resistance of copper for the same size — which is why aluminum usually lands one to two sizes larger than copper for the same job.

Voltage Drop Limits

CircuitRecommended LimitWhy
Branch circuit3%The NEC recommendation for the final run to a load
Feeder plus branch5%The combined total the NEC suggests as a ceiling
Sensitive electronics2%Tighter, where stable voltage matters most
Long DC / low-voltage runsvaries12V systems are very sensitive to drop

Where Voltage Drop Takes Over from Ampacity

CircuitAmpacity sizePast this run, upsize for drop
15 A · 120 V copper14 AWG~48 ft (then 12 AWG)
20 A · 120 V copper12 AWG~58 ft (then 10 AWG)
50 A · 240 V copper8 AWG~115 ft (then 6 AWG)
50 A · 12 V DC copper8 AWG~3 ft (then much larger)

Up to the listed distance, ampacity sets the size. Beyond it, the 3% voltage-drop limit forces a larger gauge. Higher voltage stretches that crossover much farther out — and low-voltage DC reaches it almost immediately, which is why solar and automotive runs need heavy wire.

🔍 Key Factors

What Determines the Wire Size You Need

Eight variables decide the gauge. The first three set the ampacity floor; the rest swing the voltage-drop result.

📏
Run Length
The single biggest lever. Voltage drop is directly proportional to distance — a run twice as long has twice the drop. Long circuits almost always need a larger wire than the current alone would suggest.
🔌
Wire Gauge (the output)
Bigger wire carries more current and drops less voltage — the lever you actually pull. The calculator returns the smallest gauge that clears both limits; you can always go larger.
Load Current
Drop rises in step with current. The same wire over the same distance loses more voltage to a heavy load than a light one — heavy loads and long runs are a demanding combination.
🔋
System Voltage
Drop as a percentage depends on the source voltage. The same volts lost is a small fraction of 480 V but a large fraction of 12 V — which is why low-voltage systems are so drop-sensitive.
🟠
Conductor Material
Copper conducts better than aluminum. For the same gauge, aluminum has roughly 1.6 times the resistance, so an aluminum run drops more voltage than a copper one of the same size.
🔀
Phase Type
DC and single-phase use a factor of 2 for the round-trip conductor; three-phase uses √3. The same wire and load produce a different drop depending on the system.
⚖️
Parallel Sets
Running conductors in parallel splits the current and lowers the effective resistance. Two identical sets halve the drop — a common approach on large feeders.
🌡️
Temperature
Conductor resistance rises with temperature. A wire running warm under load has slightly more resistance than the cool-table value, so real drop can edge above the calculated figure.
⚡ Conductors & Phases

Copper vs Aluminum & Phase Types

Two choices shape the result before you touch a number: the conductor metal, and the type of electrical system.

🟠
Copper
Lower R
resistance
1.93
Ω/1000ft (12 AWG)
Less drop
Per gauge
Aluminum
~1.6×
copper's R
3.18
Ω/1000ft (12 AWG)
Lighter, cheaper
Big feeders
Single-Phase
×2
distance factor
120 / 240 V
typical
Homes
Most circuits
🔌
Three-Phase
×1.732
distance factor
208 / 480 V
typical
Commercial
Industry
ChoiceEffect on DropTypical Use
CopperLower resistance, less drop per gaugeBranch circuits, most residential wiring
AluminumHigher resistance; needs a larger size to match copperService entrances and large feeders
DCFactor of 2 for the return conductorSolar, automotive, low-voltage systems
AC single-phaseFactor of 2, same as DCHomes and light commercial
AC three-phaseFactor of √3 (1.732)Commercial and industrial power
Aluminum is not a drop-in for copper: for the same load it usually needs to be one or two AWG sizes larger, and it must land on listed AL or AL/CU-rated terminals with anti-oxidant compound. The calculator already applies aluminum's higher resistance and lower ampacity — switch the material and watch the recommended size step up.
🛠️ Wire Sizing

How to Size Wire for a Run: A Phase-by-Phase Roadmap

Picking a wire size is two questions answered in order — can it carry the current, and can it keep the drop in check. Here is the path.

Phase 1 · Start With the Load
Know the current and the distance

Find the load's current draw in amps and measure the one-way run from the source to the load. These two figures, with the system voltage, define the whole problem.

Gather: current, one-way distance, voltage
Phase 2 · Size for Ampacity First
Pick a wire that can carry the current

Every wire size has an ampacity — the current it can safely carry. Start with the smallest gauge rated for your load current. This is the safety floor, set by code, before drop is even considered.

Rule: never go below the code ampacity
Phase 3 · Check the Voltage Drop
Run that gauge through the calculator

The calculator computes the drop for the ampacity-sized wire automatically. If it lands under 3%, that gauge works on both counts. If not, the run is too long for that size — and the tool moves to the next size for you.

Target: 3% or less on a branch circuit
Phase 4 · Upsize Until It Passes
Step up a gauge and recheck

The calculator steps up one size at a time until the drop clears your limit, then reports that gauge as the voltage-drop size. The final recommendation is whichever is larger — the size that satisfies both ampacity and voltage drop.

Pro move: let the stricter of the two rules win
💸 The Cost

The Cost of the Wrong Wire Size

Undersize and you pay in heat and hardware; oversize and you pay in copper. The right size is the cheapest path over the life of the circuit.

An undersized wire that still passes ampacity can lose real voltage over distance — energy turned into heat instead of useful work, billed year after year for nothing but a warm cable. Worse, a wire that is genuinely too small for its load runs hot, ages its insulation early, and trips breakers. Sizing it right the first time avoids both.

The opposite mistake costs too. Copper is expensive, and jumping two sizes "to be safe" on every run adds up fast across a job. The goal is not the biggest wire — it is the smallest wire that clears both the ampacity and voltage-drop limits, which is exactly what the calculator returns.

🔥
Wasted Energy
Lost as heat in the wire
CauseDrop × current
Shows upOn the bill
FixLarger wire
A steady, ongoing loss
⚙️
Equipment Strain
Motors and electronics
CauseLow voltage
Shows upEarly failures
FixStay under 3%
A hidden long-term cost
🔌
Upsizing the Wire
The one-time cure
CauseBigger gauge
Shows upUp-front cost
PaybackYears of savings
Pay once, save for decades
Size before you pull: wire is cheap to change on paper and expensive to change in a wall. Settling the gauge before installation costs only the price difference in copper. Discovering an undersized run after the cable is buried means tearing it out and starting over.
💡 Real Examples

Real Wire-Sizing Examples

Three circuits, three different binding constraints — each worked through with verified math so you can check your own.

EXAMPLE 1A 50 A EV Charger, 120 ft Away
⚡ Load: 50 A 🔋 System: 240 V single-phase 📏 Distance: 120 ft 🟠 Material: copper, 75°C
Recommended Size
6 AWG · 2.0% drop
Ampacity → 8 AWG · Drop on 8 AWG = 3.1% → upsize to 6 AWG
🟡 Voltage Drop Sets the Size 8 AWG copper carries 50 A safely, but over 120 feet it drops 3.1% — just past the limit. Bumping to 6 AWG brings the drop to 2.0%. This is the classic long-run case where distance, not amperage, decides the gauge.
EXAMPLE 2A 20 A Kitchen Circuit, 40 ft
⚡ Load: 20 A 🔋 System: 120 V single-phase 📏 Distance: 40 ft 🟠 Material: copper, 75°C
Recommended Size
12 AWG · 2.1% drop
Ampacity → 12 AWG · Drop on 12 AWG = 2.1% → 12 AWG clears both
🟢 Ampacity Sets the Size On a short run, voltage drop is a non-issue. 12 AWG copper is the code minimum for a 20-amp circuit and its drop at 40 feet is only 2.1%. Both checks agree, so 12 AWG is the answer — no upsizing needed.
EXAMPLE 3A 50 A Aluminum Subpanel Feeder, 200 ft
⚡ Load: 50 A 🔋 System: 240 V single-phase 📏 Distance: 200 ft ⚪ Material: aluminum, 75°C
Recommended Size
3 AWG · 2.7% drop
Ampacity → 6 AWG · Drop on 6 AWG = 5.4% → upsize to 3 AWG
🟡 Aluminum + Distance Force a Big Jump 6 AWG aluminum is rated for 50 A, but at 200 feet it drops 5.4% — well over the limit. Aluminum's higher resistance and the long run push the size all the way to 3 AWG, where the drop falls to 2.7%. A copper run here would need only 6 AWG.
📋 Best Practice

Wire-Sizing Best Practices

Good wire sizing is a handful of habits applied before the cable is pulled. These are the ones that matter most.

The first habit is checking drop on every run that is even moderately long. Short circuits rarely have a problem, so they get a pass — but a run of fifty feet or more, especially at 120 volts, deserves a quick calculation. Catching a marginal circuit on paper is free; catching it after the wall is closed is not.

The second is treating ampacity and voltage drop as two separate hurdles, both of which the wire must clear. A gauge can be perfectly safe for the current and still drop too much voltage over distance. When the two rules disagree, the larger wire wins — that is the size that satisfies both.

Six Habits for Sizing Wire Right

📏
Check every long run. Any circuit over about fifty feet deserves a voltage drop calculation before the wire size is locked in.
🔌
Size for ampacity and drop both. The wire has to carry the current safely and keep the drop in range — let the stricter of the two set the gauge.
⬆️
Upsize early on long runs. When a circuit is long, plan on a larger gauge from the start rather than discovering the shortfall after installation.
🟠
Account for the conductor metal. Aluminum needs a size or two larger than copper to land at the same voltage drop — never swap them gauge-for-gauge.
🔋
Watch low-voltage runs closely. A 12-volt DC circuit hits its drop limit in a fraction of the distance a 120-volt one would — they need heavier wire than people expect.
📋
Follow the local code. Voltage drop guidance and wire sizing rules are set by the NEC and local amendments — confirm the requirements that apply to your job.
⚠️ Limitations

When This Calculator Is the Wrong Tool

The ampacity and drop math here is exact, but a real installation has factors a quick calculation does not capture. Here is where the output needs an expert's eye.

1. It uses resistance only, not full impedance. On AC circuits, conductors also have reactance, and in steel conduit that reactance is significant. This calculator works from DC resistance, which is accurate for most planning but slightly optimistic for large AC conductors in metallic conduit.

2. It does not apply derating. Ampacity here comes straight from NEC Table 310.16. It does not reduce for more than three current-carrying conductors in a raceway, high ambient temperature, or conduit fill — all of which can require a larger conductor. On bundled or hot installs, apply the derating factors.

3. Resistance values are at a reference temperature. Conductor resistance rises as the wire heats under load. The table values assume a standard temperature, so a hot circuit will drop slightly more voltage than calculated.

4. It assumes a balanced, steady load. The math is for a constant current draw. Motors drawing heavy startup current, or unbalanced three-phase loads, behave differently and need a more detailed analysis.

Where to go instead: for code-critical work, a licensed electrician and the full NEC are the authority — including derating, Chapter 9 Table 9 for AC impedance in conduit, and the dwelling-service allowances of 310.12. This calculator is a fast, accurate first pass for sizing wire by ampacity and voltage drop, not a substitute for a code-compliant design.

📚 Glossary

Electrical Terms You'll See On This Page

Quick reference for the electrical terms used throughout this wire size calculator.

Voltage Drop
The voltage lost in a conductor as current flows through its resistance, between the source and the load.
Resistance
A conductor's opposition to current flow, measured in ohms. It rises with length and falls with wire size.
AWG
American Wire Gauge — the standard sizing system for wire. A smaller AWG number means a thicker wire.
Ampacity
The maximum current a conductor can carry continuously without overheating, fixed by NEC Table 310.16 for each size, material and temperature rating. It sets the minimum wire size for a given load.
Termination Rating
The temperature rating of the terminals a wire lands on — 60, 75 or 90°C. Conductor sizing uses the column matching the lowest-rated component, usually 75°C.
Ohm's Law
The relationship V = I × R — voltage equals current times resistance — the basis of the drop formula.
One-Way Distance
The length of the run measured in a single direction, from the source to the load.
Phase Factor
The multiplier in the drop formula — 2 for DC and single-phase, 1.732 for three-phase.
Conductor
The metal wire that carries current — usually copper or aluminum.
NEC
The National Electrical Code, the US standard for electrical installation, including voltage drop guidance.
Parallel Sets
Two or more identical conductor runs wired side by side to share current and lower effective resistance.
Branch Circuit
The final wiring run between the last overcurrent device and the load it serves.
Feeder
A circuit between the service equipment and a branch-circuit panel further down the line.
Load Current
The current, in amps, that the connected equipment draws from the circuit.
Voltage at Load
The voltage actually reaching the equipment — the source voltage minus the voltage drop.
❓ FAQ

Frequently Asked Questions

The most common questions about sizing electrical wire.

How do I calculate what wire size I need?

Wire size is set by two checks. First, the conductor's ampacity must meet the load current using NEC Table 310.16 at your termination rating (usually 75°C). Second, the wire must keep voltage drop under about 3% over the run. The correct size is the larger of the two results — which is exactly what this calculator returns.

What size wire do I need for 50 amps?

For a 50-amp circuit, use 8 AWG copper (rated 50 A at 75°C) or 6 AWG aluminum. On long runs the voltage-drop check can push this to 6 AWG copper, which is why many electricians use 6 AWG for a 50-amp range or EV charger on a longer pull.

Does wire size depend on distance?

Yes. Ampacity sets the minimum size for the current, but on runs longer than about 50 feet voltage drop often requires a larger wire. The longer the run, the bigger the conductor needed to keep drop within the 3% guideline. Higher system voltage stretches that crossover much farther out.

Do I need a bigger wire for aluminum than copper?

Yes. Aluminum carries less current and has higher resistance than copper, so it usually needs to be one or two AWG sizes larger for the same load and distance. Aluminum also requires listed AL/CU connectors and anti-oxidant paste at terminations.

What is the 3% voltage drop rule?

The NEC recommends keeping voltage drop at or below 3% on a branch circuit and 5% combined across feeder and branch. It is a recommendation rather than a hard rule, but staying within it protects equipment performance and efficiency. You can tighten the limit to 2% for sensitive electronics.

Is this wire size calculator NEC compliant?

The ampacity values follow NEC Table 310.16 and the voltage-drop math uses standard conductor resistance. It is an estimating aid, not a substitute for a licensed electrician or local code. Always confirm derating, conduit fill, and termination ratings for your installation.

What size wire do I need for 100 amps?

A 100-amp circuit needs 3 AWG copper or 1 AWG aluminum by NEC Table 310.16. For a 100-amp dwelling service or feeder, NEC 310.12 permits the reduced sizes of 4 AWG copper or 2 AWG aluminum. Long feeders may need to go larger for voltage drop.

What size wire for a 20 amp or 30 amp circuit?

Use 12 AWG copper for a 20-amp circuit and 10 AWG copper for a 30-amp circuit at the 75°C rating. These are the most common branch-circuit sizes — 12 AWG for kitchen and bathroom receptacles, 10 AWG for dryers, water heaters and small A/C units.

What does the termination rating (60/75/90°C) change?

It selects which ampacity column applies. Most modern breakers and lugs are rated 75°C, so conductor sizing uses the 75°C values even if the wire's insulation is rated 90°C. The 90°C column is mainly used as a starting point for derating, not for final sizing.

Should I size for the breaker or the load?

Size the wire so its ampacity is at least the breaker rating it is protected by — the breaker and conductor work as a pair. For continuous loads (running three hours or more), size both for 125% of the load. This calculator sizes to the current you enter, so enter the breaker rating or the 125% figure as appropriate.

🔌 Free · Instant · No Sign-Up

Size Your Wire
in 30 Seconds

Enter the load, distance, voltage and material — get the minimum AWG from NEC ampacity and voltage drop, with the size required by each. All free.

Size My Wire — Free Takes 30 seconds · No account needed · Copper & aluminum
Minimum AWG, both checks
Copper & aluminum
AC & DC, all phases
NEC 310.16 ampacity
Free forever
Disclaimer: The recommended wire size is computed from NEC Table 310.16 ampacity and exact voltage-drop arithmetic for the figures you enter, using standard conductor resistance values. It uses DC resistance, which is very close to the true value for typical building circuits; large conductors and steel conduit add AC effects that a full NEC impedance method accounts for. This tool provides estimates for educational and planning purposes only. It does not apply conductor derating, conduit fill, or the dwelling-service allowances of NEC 310.12, and is not a substitute for a licensed electrician. Wire sizing, circuit protection, and installation are governed by electrical codes — always confirm the requirements that apply to your project and work with a qualified professional.