🔌 Wire Size Calculator
Find the minimum wire gauge (AWG) for any circuit — from load current, run length, voltage, and conductor material. Checks both NEC ampacity and the 3% voltage-drop limit, for copper and aluminum. Free, no sign-up.
A wire size calculator finds the smallest wire gauge that can safely carry a given load. It checks two things: the conductor's ampacity — how much current it can carry per NEC Table 310.16 — and the voltage drop over the run. The correct wire size is whichever of the two is larger. The core checks are:
How to size a wire in 3 steps:
- Enter the load current, voltage, one-way distance, and conductor material.
- Pick the termination rating (75°C is typical) and your max voltage drop (3% by default).
- Click Calculate for the recommended AWG, with ampacity headroom and the resulting drop %.
For example, a 50 A load at 240 V over a 100-foot copper run needs 8 AWG — it carries 50 A at the 75°C rating and drops just 2.6%, within the 3% limit.
Wire Size Calculator
Enter load current, distance and material — get the minimum AWG wire size.
Know the Right Wire Size –
Before You Pull the Cable
Pick a wire too small and it overheats; too small for the distance and the voltage sags. This free calculator turns your load, run length, voltage and material into the minimum AWG — checking both NEC ampacity and the 3% voltage-drop limit, and recommending the larger of the two.
⚡ Try the Calculator NowThe Right Wire Size Is Two Questions, Not One
Choosing a wire gauge feels like it should be one lookup, but it is really two. The wire has to carry the current without overheating, and it has to deliver that current over the distance without the voltage sagging too far. The correct size is whichever of those two answers is larger.
The first question is ampacity — the current a conductor can carry continuously without overheating, fixed by the NEC for each size, material and temperature rating. The second is voltage drop — the voltage lost to the wire's resistance over the run, which grows with distance and current. A gauge can be perfectly safe for the amps and still drop too much voltage over a long pull.
This Wire Size Calculator answers both at once. Enter the load current, voltage, one-way distance and material; it finds the smallest AWG that meets the NEC ampacity table and the smallest that stays under your voltage-drop limit, then recommends whichever is larger — the size that satisfies both rules.
How the Wire Size Calculator Works
Fill in the circuit, click once. Here is what each field does and how the recommendation is reached.
Set Phase & Material
Choose DC, AC single-phase, or AC three-phase, and whether the conductor is copper or aluminum. Each combination changes both the ampacity and the voltage-drop math.
🟠 Copper carries more current than aluminum of the same size.Pick the Termination Rating
60, 75, or 90°C — the rating of the terminals the wire lands on. Most modern breakers and lugs are 75°C, which is the default and the safe choice when unsure.
🌡️ Sizing follows the lowest-rated part in the circuit.Enter Voltage & Load Current
The system voltage (12, 120, 240, 480…) and the current the load draws in amps. Ampacity is checked against the amps; the drop is measured against the voltage.
⚡ More amps push the size up on both counts.Enter the One-Way Distance
The distance from the source to the load, measured one direction only. The calculator doubles it for the return conductor on DC and single-phase circuits.
Set the Max Voltage Drop
The drop limit you want to hold to — 3% by default, the NEC branch-circuit recommendation. Tighten it to 2% for sensitive electronics or long low-voltage runs.
✅ 3% branch · 5% feeder + branch combinedCalculate — Read the Size
You get the recommended AWG, the size required by ampacity, the size required by voltage drop, the ampacity headroom, and the resulting drop at the chosen gauge.
📐 Recommended = larger of the two required sizesHow Wire Sizing Works: Ampacity and Voltage Drop
Two independent checks decide the gauge. The calculator runs both and takes the larger result.
Check 1 — ampacity. Every wire size has an ampacity: the current it can carry continuously without its insulation overheating. The NEC fixes these values in Table 310.16 for each material and temperature rating. The calculator scans from the smallest gauge up and picks the first one whose ampacity meets your load current. That is the safety floor.
Check 2 — voltage drop. Drop is Ohm's law over the run: 2 × current × resistance-per-foot × one-way distance for DC and single-phase (the 2 covers the return conductor), or √3 × the rest for three-phase. The calculator finds the smallest gauge whose drop stays under your limit, expressed as a percentage of the supply voltage.
Taking the larger. The two checks rarely agree. Short runs are limited by ampacity; long runs by voltage drop. The recommended size is whichever is bigger, because the wire must clear both hurdles. The result panel labels which one was binding so you can see why.
A worked example. A 50-amp load at 240 V, copper, 100 feet one-way. Ampacity needs 8 AWG (rated 50 A at 75°C). Voltage drop on 8 AWG is 2 × 50 × 0.628 × (100 ÷ 1000) = 6.28 V, or 2.6% of 240 V — under the 3% limit. Both checks land on 8 AWG, so 8 AWG is the answer.
Parallel conductor sets change the drop term. Running two identical sets side by side halves the effective resistance, which halves the drop — useful on large feeders. Enable Advanced mode to set the number of sets; the calculator divides the resistance accordingly before checking the limit.
Wire Size by Amps & Ampacity Charts
The quick lookup most people want first — wire size by amperage — plus the ampacity and resistance values the calculator works from.
Wire Size by Amperage (Copper & Aluminum, 75°C)
| Load Current | Copper AWG | Aluminum AWG | Common Use |
|---|---|---|---|
| 15 A | 14 AWG | 12 AWG | Lighting, general receptacles |
| 20 A | 12 AWG | 10 AWG | Kitchen & bathroom circuits |
| 30 A | 10 AWG | 8 AWG | Dryer, water heater, A/C |
| 40 A | 8 AWG | 8 AWG | Range, large A/C |
| 50 A | 8 AWG | 6 AWG | Range, EV charger, subpanel |
| 60 A | 6 AWG | 4 AWG | Small subpanel, hot tub |
| 100 A | 3 AWG | 1 AWG | Subpanel feeder |
| 150 A | 1/0 AWG | 3/0 AWG | Large feeder |
| 200 A | 3/0 AWG | 250 kcmil | Main service feeder |
These are NEC Table 310.16 sizes at the 75°C column, with the small-conductor limits of NEC 240.4(D) applied (14 AWG max 15 A, 12 AWG max 20 A, 10 AWG max 30 A copper) — the size needed to carry the current on a short run. Long runs may need a larger gauge for voltage drop, which is what the calculator above checks. Note that dwelling service and feeder conductors may use the reduced sizes allowed by NEC 310.12 (for example, 4 AWG copper or 2 AWG aluminum for a 100-amp dwelling service).
Conductor Resistance (Ω per 1000 ft)
| Wire Size | Copper (Ω/1000 ft) | Aluminum (Ω/1000 ft) |
|---|---|---|
| 14 AWG | 3.07 | 5.06 |
| 12 AWG | 1.93 | 3.18 |
| 10 AWG | 1.21 | 2.00 |
| 8 AWG | 0.764 | 1.26 |
| 6 AWG | 0.491 | 0.808 |
| 4 AWG | 0.308 | 0.508 |
| 2 AWG | 0.194 | 0.319 |
| 1/0 AWG | 0.122 | 0.201 |
| 2/0 AWG | 0.0967 | 0.159 |
| 4/0 AWG | 0.0608 | 0.100 |
Reading the resistance table: a smaller AWG number is a thicker wire with lower resistance, so it drops less voltage. Aluminum runs about 1.6× the resistance of copper for the same size — which is why aluminum usually lands one to two sizes larger than copper for the same job.
Voltage Drop Limits
| Circuit | Recommended Limit | Why |
|---|---|---|
| Branch circuit | 3% | The NEC recommendation for the final run to a load |
| Feeder plus branch | 5% | The combined total the NEC suggests as a ceiling |
| Sensitive electronics | 2% | Tighter, where stable voltage matters most |
| Long DC / low-voltage runs | varies | 12V systems are very sensitive to drop |
Where Voltage Drop Takes Over from Ampacity
| Circuit | Ampacity size | Past this run, upsize for drop |
|---|---|---|
| 15 A · 120 V copper | 14 AWG | ~48 ft (then 12 AWG) |
| 20 A · 120 V copper | 12 AWG | ~58 ft (then 10 AWG) |
| 50 A · 240 V copper | 8 AWG | ~115 ft (then 6 AWG) |
| 50 A · 12 V DC copper | 8 AWG | ~3 ft (then much larger) |
Up to the listed distance, ampacity sets the size. Beyond it, the 3% voltage-drop limit forces a larger gauge. Higher voltage stretches that crossover much farther out — and low-voltage DC reaches it almost immediately, which is why solar and automotive runs need heavy wire.
What Determines the Wire Size You Need
Eight variables decide the gauge. The first three set the ampacity floor; the rest swing the voltage-drop result.
Copper vs Aluminum & Phase Types
Two choices shape the result before you touch a number: the conductor metal, and the type of electrical system.
| Choice | Effect on Drop | Typical Use |
|---|---|---|
| Copper | Lower resistance, less drop per gauge | Branch circuits, most residential wiring |
| Aluminum | Higher resistance; needs a larger size to match copper | Service entrances and large feeders |
| DC | Factor of 2 for the return conductor | Solar, automotive, low-voltage systems |
| AC single-phase | Factor of 2, same as DC | Homes and light commercial |
| AC three-phase | Factor of √3 (1.732) | Commercial and industrial power |
How to Size Wire for a Run: A Phase-by-Phase Roadmap
Picking a wire size is two questions answered in order — can it carry the current, and can it keep the drop in check. Here is the path.
Find the load's current draw in amps and measure the one-way run from the source to the load. These two figures, with the system voltage, define the whole problem.
Every wire size has an ampacity — the current it can safely carry. Start with the smallest gauge rated for your load current. This is the safety floor, set by code, before drop is even considered.
The calculator computes the drop for the ampacity-sized wire automatically. If it lands under 3%, that gauge works on both counts. If not, the run is too long for that size — and the tool moves to the next size for you.
The calculator steps up one size at a time until the drop clears your limit, then reports that gauge as the voltage-drop size. The final recommendation is whichever is larger — the size that satisfies both ampacity and voltage drop.
The Cost of the Wrong Wire Size
Undersize and you pay in heat and hardware; oversize and you pay in copper. The right size is the cheapest path over the life of the circuit.
An undersized wire that still passes ampacity can lose real voltage over distance — energy turned into heat instead of useful work, billed year after year for nothing but a warm cable. Worse, a wire that is genuinely too small for its load runs hot, ages its insulation early, and trips breakers. Sizing it right the first time avoids both.
The opposite mistake costs too. Copper is expensive, and jumping two sizes "to be safe" on every run adds up fast across a job. The goal is not the biggest wire — it is the smallest wire that clears both the ampacity and voltage-drop limits, which is exactly what the calculator returns.
Real Wire-Sizing Examples
Three circuits, three different binding constraints — each worked through with verified math so you can check your own.
Wire-Sizing Best Practices
Good wire sizing is a handful of habits applied before the cable is pulled. These are the ones that matter most.
The first habit is checking drop on every run that is even moderately long. Short circuits rarely have a problem, so they get a pass — but a run of fifty feet or more, especially at 120 volts, deserves a quick calculation. Catching a marginal circuit on paper is free; catching it after the wall is closed is not.
The second is treating ampacity and voltage drop as two separate hurdles, both of which the wire must clear. A gauge can be perfectly safe for the current and still drop too much voltage over distance. When the two rules disagree, the larger wire wins — that is the size that satisfies both.
Six Habits for Sizing Wire Right
When This Calculator Is the Wrong Tool
The ampacity and drop math here is exact, but a real installation has factors a quick calculation does not capture. Here is where the output needs an expert's eye.
1. It uses resistance only, not full impedance. On AC circuits, conductors also have reactance, and in steel conduit that reactance is significant. This calculator works from DC resistance, which is accurate for most planning but slightly optimistic for large AC conductors in metallic conduit.
2. It does not apply derating. Ampacity here comes straight from NEC Table 310.16. It does not reduce for more than three current-carrying conductors in a raceway, high ambient temperature, or conduit fill — all of which can require a larger conductor. On bundled or hot installs, apply the derating factors.
3. Resistance values are at a reference temperature. Conductor resistance rises as the wire heats under load. The table values assume a standard temperature, so a hot circuit will drop slightly more voltage than calculated.
4. It assumes a balanced, steady load. The math is for a constant current draw. Motors drawing heavy startup current, or unbalanced three-phase loads, behave differently and need a more detailed analysis.
Where to go instead: for code-critical work, a licensed electrician and the full NEC are the authority — including derating, Chapter 9 Table 9 for AC impedance in conduit, and the dwelling-service allowances of 310.12. This calculator is a fast, accurate first pass for sizing wire by ampacity and voltage drop, not a substitute for a code-compliant design.
Electrical Terms You'll See On This Page
Quick reference for the electrical terms used throughout this wire size calculator.
- Voltage Drop
- The voltage lost in a conductor as current flows through its resistance, between the source and the load.
- Resistance
- A conductor's opposition to current flow, measured in ohms. It rises with length and falls with wire size.
- AWG
- American Wire Gauge — the standard sizing system for wire. A smaller AWG number means a thicker wire.
- Ampacity
- The maximum current a conductor can carry continuously without overheating, fixed by NEC Table 310.16 for each size, material and temperature rating. It sets the minimum wire size for a given load.
- Termination Rating
- The temperature rating of the terminals a wire lands on — 60, 75 or 90°C. Conductor sizing uses the column matching the lowest-rated component, usually 75°C.
- Ohm's Law
- The relationship V = I × R — voltage equals current times resistance — the basis of the drop formula.
- One-Way Distance
- The length of the run measured in a single direction, from the source to the load.
- Phase Factor
- The multiplier in the drop formula — 2 for DC and single-phase, 1.732 for three-phase.
- Conductor
- The metal wire that carries current — usually copper or aluminum.
- NEC
- The National Electrical Code, the US standard for electrical installation, including voltage drop guidance.
- Parallel Sets
- Two or more identical conductor runs wired side by side to share current and lower effective resistance.
- Branch Circuit
- The final wiring run between the last overcurrent device and the load it serves.
- Feeder
- A circuit between the service equipment and a branch-circuit panel further down the line.
- Load Current
- The current, in amps, that the connected equipment draws from the circuit.
- Voltage at Load
- The voltage actually reaching the equipment — the source voltage minus the voltage drop.
Frequently Asked Questions
The most common questions about sizing electrical wire.
How do I calculate what wire size I need?
Wire size is set by two checks. First, the conductor's ampacity must meet the load current using NEC Table 310.16 at your termination rating (usually 75°C). Second, the wire must keep voltage drop under about 3% over the run. The correct size is the larger of the two results — which is exactly what this calculator returns.
What size wire do I need for 50 amps?
For a 50-amp circuit, use 8 AWG copper (rated 50 A at 75°C) or 6 AWG aluminum. On long runs the voltage-drop check can push this to 6 AWG copper, which is why many electricians use 6 AWG for a 50-amp range or EV charger on a longer pull.
Does wire size depend on distance?
Yes. Ampacity sets the minimum size for the current, but on runs longer than about 50 feet voltage drop often requires a larger wire. The longer the run, the bigger the conductor needed to keep drop within the 3% guideline. Higher system voltage stretches that crossover much farther out.
Do I need a bigger wire for aluminum than copper?
Yes. Aluminum carries less current and has higher resistance than copper, so it usually needs to be one or two AWG sizes larger for the same load and distance. Aluminum also requires listed AL/CU connectors and anti-oxidant paste at terminations.
What is the 3% voltage drop rule?
The NEC recommends keeping voltage drop at or below 3% on a branch circuit and 5% combined across feeder and branch. It is a recommendation rather than a hard rule, but staying within it protects equipment performance and efficiency. You can tighten the limit to 2% for sensitive electronics.
Is this wire size calculator NEC compliant?
The ampacity values follow NEC Table 310.16 and the voltage-drop math uses standard conductor resistance. It is an estimating aid, not a substitute for a licensed electrician or local code. Always confirm derating, conduit fill, and termination ratings for your installation.
What size wire do I need for 100 amps?
A 100-amp circuit needs 3 AWG copper or 1 AWG aluminum by NEC Table 310.16. For a 100-amp dwelling service or feeder, NEC 310.12 permits the reduced sizes of 4 AWG copper or 2 AWG aluminum. Long feeders may need to go larger for voltage drop.
What size wire for a 20 amp or 30 amp circuit?
Use 12 AWG copper for a 20-amp circuit and 10 AWG copper for a 30-amp circuit at the 75°C rating. These are the most common branch-circuit sizes — 12 AWG for kitchen and bathroom receptacles, 10 AWG for dryers, water heaters and small A/C units.
What does the termination rating (60/75/90°C) change?
It selects which ampacity column applies. Most modern breakers and lugs are rated 75°C, so conductor sizing uses the 75°C values even if the wire's insulation is rated 90°C. The 90°C column is mainly used as a starting point for derating, not for final sizing.
Should I size for the breaker or the load?
Size the wire so its ampacity is at least the breaker rating it is protected by — the breaker and conductor work as a pair. For continuous loads (running three hours or more), size both for 125% of the load. This calculator sizes to the current you enter, so enter the breaker rating or the 125% figure as appropriate.
The Electrical Cluster & More
Wire sizing is one part of an electrical job. Start with its sibling calculator and the guides behind the numbers, then the rest of the build.
Size Your Wire
in 30 Seconds
Enter the load, distance, voltage and material — get the minimum AWG from NEC ampacity and voltage drop, with the size required by each. All free.
Size My Wire — Free Takes 30 seconds · No account needed · Copper & aluminum